1. The OS-550T is an occupancy sensor designed for automatic operation control of HVAC system. This occupancy sensor delivers a changeover relay contact output to control the HVAC operation according to the occupancy status of the area.
2. In addition to all standard features of OS-550, this sensor provides high/low temperature setbacks to prevent the room temperature becoming too high or too low during unoccupied period. The sensor can be wall or ceiling mounted with the mounting bracket.
1. Power supply 24 2 VAC/DC. 2. Detection range 15 x 15 m at 25C. 3. Relay output Form C, 5A / NO, 3A / NC resistive. 4. Current drain 20 mA @24 VDC. 5. Temp. setbacks High: 30 / 28 / 26C, Low: 15 / 13 / 11C. 6. Mounting height 1.8 ~ 3.6 m. 7. ON delay 0 - 10" - 30" - 1' - 5' - 10' selectable. 8. OFF delay 10" - 1' - 5' - 10' - 20' - 30' selectable. 9. Detectable speed 0.1~ 3 m/sec.(0.3~10 ft/sec.). 10. RFI immunity Av. 20 V/m (10~1,000 MHz). 11. Humidity 95% RH max. 12. Temperature -10C ~ 60C (14F ~ 140F). 13. Dimensions 112 x 66 x 45 mm (4.4 x 2.6 x 1.8").
1. Dual element infrared sensor.
2. Superior RFI / EMI immunity.
3. Temperature compensation.
4. Programmable ON & OFF delays.
5. High density detection zones.
6. Disabled walk test LED.
7. Mounting bracket included.
8. Form C changeover relay output.
9. High-low temperature setbacks.
10. Dual zone look down detection.