Specially for outdoor equipment
Intelligent logic assemble function programming, it is suitable for all kinds of load and premises. The product lines have complete series and are all CE certified. Also, its with compact size, high efficiency, and easier to operation. Electrical and servo module mass producing, with several patents and anti-mistake circuit design, the producing procedure meet international standard, with high reliability quality and long MTBF.
Model No. (PSO-) | 310 X/N/Y | 315 X/N/Y | 320 X/N/Y | 330 X/N/Y | 345 X/N/Y | 360 X/N/Y | 375 X/N/Y | 3100 X/N/Y | 3120 X/N/Y | 3150 X/N | 3180 X/N | 3200 X/N | 3250 X/N | 3300 X/N | 3400 X/N | ||
Capacity (KVA) | 10 | 15 | 20 | 30 | 45 | 60 | 75 | 100 | 120 | 150 | 180 | 200 | 250 | 300 | 400 | ||
Voltage | X2 : 3ψ 3W 200V, 220V, 230V, 240V system (I/P and O/P are the same) X3 : 3ψ 3W 380V, 400V system (I/P and O/P are the same) X4 : 3ψ 3W 415V, 440V system (I/P and O/P are the same) N1 : 3ψ 4W 110/190V, 120/208V, 127/220V system (I/P and O/P are the same) N2 : 3ψ 4W 220/380V, 230/400V, 240/415V system (I/P and O/P are the same) (Indicate phase voltage) N3 : 3ψ 4W 220/380V, 230/400V, 240/415V system (I/P and O/P are the same) (Indicate line voltage) Y : Input 3ψ 3W 380V, Output 3ψ 3W 220V (I/P and O/P are different) Y2 : Input 3ψ 3W , Output 3ψ 4W (I/P and O/P are different) | ||||||||||||||||
Input Range | Nominal Voltage: ±15% (±20%~±40% can be customized) Frequency: 50/60Hz±5% | ||||||||||||||||
Output Accuracy | ≦1% | ||||||||||||||||
Power Factor | 0.95~1 | ||||||||||||||||
Efficiency | ≧98% | ||||||||||||||||
Response Time | <0.1 Second | ||||||||||||||||
Waveform Distortion | No distortion | ||||||||||||||||
Protection | High Voltage | Standard Feature (can be Various / Multi / Big range pre-set and LED displayed) | |||||||||||||||
Low Voltage | Standard Feature (can be Various / Multi / Big range pre-set and LED displayed) | ||||||||||||||||
Phase Failure | Standard Feature (can be Various / Multi / Big range pre-set and LED displayed) | ||||||||||||||||
Bypass | Standard Feature (with Phase Failure, Instant Trip, High / Low Voltage Protection at work) | ||||||||||||||||
Indicators | Power | Standard Feature | |||||||||||||||
Voltage | Standard Feature | ||||||||||||||||
Abnormal | Standard Feature | ||||||||||||||||
Overload | 150% for 10 seconds | ||||||||||||||||
Environment | Temperature: 0℃~45℃ Humidity: 0%~95% RH (Non-Condensing) |