100% made in Taiwan, the On Line UPS system is suitable for load of SMT, OA quipment, automatic testing system, computer and related products. In IGBT/PWM advance and module design, the equipment is highly reliable, excellent quality and exceptional long MTBF.
Model No. | P-1000 | P-1000R | P-2000 | P-2000R | P-3000 | P-3000R | |||||||||
Capacity | 1KVA/700W | 2KVA/1400W | 3KVA/2100W | ||||||||||||
Input | Voltage Range | 110V system :80V~143V (100% load), 65V~80V (70% load) 220V system: 160V~286V (100% load),130V~160V (70% load) | |||||||||||||
Frequency | 50Hz or 60Hz±5% (auto adjusting) | ||||||||||||||
Power Factor | >0.95 | >0.97 | |||||||||||||
Battery | DC Voltage | 36VDC | 96VDC | ||||||||||||
Type | Maintenance free sealed lead-acid battery | ||||||||||||||
Back Up (Full Load) | 7mins | 8mins | 13mins | 5mins | 7mins | ||||||||||
Back Up (Half Load) | 18mins | 23mins | 32mins | 13mins | 18mins | ||||||||||
Recharging Time | 8 hours to 90% | ||||||||||||||
Output | Voltage | 110V system: 100V,110V,115V,120V 220V system: 200V,220V,230V,240V | |||||||||||||
Frequency | Synchronized (line mode), 50Hz or 60Hz±0.5% (battery mode) | ||||||||||||||
Waveform | True sine wave | ||||||||||||||
Voltage Regulation | ±2% | ||||||||||||||
Distortion | |||||||||||||||
Overload Capability | 108%~150% for 1 min., >150% for 200ms | ||||||||||||||
Transfer time | Black Out or Power Recovered | 0ms | |||||||||||||
UPS to Bypass or Reversed Transfer | <4ms | ||||||||||||||
Overload Disappeared | Become UPS supply automatically | ||||||||||||||
Noise | At 1 Meter | ≦40db | ≦50db | ||||||||||||
Indicators | LED | Line(green), Inverter(green), Bypass(orange), Fault(red), Load %(5 LEDs), Battery(orange), Battery %(5 LEDS) | |||||||||||||
Remote LCD panel | Mini detachable LCD panel with 6 feet wire (option) | ||||||||||||||
Audible Alarm | Battery Mode | Beeping every 4 seconds (reset), and per second when battery low | |||||||||||||
Fault | Beeping continuously | ||||||||||||||
Overload | 108%~150% per second, and 150% continuously | ||||||||||||||
Auto-Restart | When mains black out and UPS turned off, it will auto-restart after mains recover | ||||||||||||||
Interface | RS-232(DB9) | UPSlion 2000 monitoring software | |||||||||||||
Options | Novell,AS400,SNMP,Windows NT,UNIX等 | ||||||||||||||
Other Function | All operation need to press 2 buttons, with battery function testing and mute button | ||||||||||||||
Environment | Temperature, Humidity | Temperature: 10℃~45℃ Humidity: 20%~90% RH (Non-Condensing) | |||||||||||||
Weight | KGS | 14 | 16.4 | 29 | 10.5+28.6 | 29 | 10.5+28.6 | ||||||||
Dimension | WxHxD (cm) | 16x24x41 | 44x88x47 | 16x37x47 | (44x9x47)x2 | 16x37x47 | (44x9x47)x2 |