◦Multiple Microprocessor design base
◦Detachable control panel with LCD
◦Unity input power factor and wide input range
◦Robust design with output transformer
◦True sine-wave double conversion on-line UPS
◦DC start and automatic self-diagnostic function
◦RS232 communication port and built-in SNMP slot
◦High efficiency design to save electricity
◦Low heat dissipation in long term operation
◦Designed to operate under harsh environment
◦Enhanced protections against lighting surges, disturbances etc..
Model (LCD Series) | UHT-103/ UHR-103 | UHT-203/ UHR-203 | UHT-303/ UHR-303 | ||||
Model (LED Series) | UHT-103L/ UHR-103L | UHT-203L/ UHR-203L | UHT-303L/ UHR-303L | ||||
Input | Capacity | 1KVA/700W | 2KVA/1.4KW | 3KVA/2.1KW | |||
Phase | Single Phase | ||||||
Nominal Voltage | 220Vac/110Vac | ||||||
Voltage Range | 160-300Vac(70%-100%load),140-300Vac (50%-70% load), 118-300Vac (0%-50% load) | ||||||
Frequency | 50Hz / 60Hz ± 4Hz | ||||||
Power Factor | ≥0.95 | ≥0.97 | |||||
Output | Voltage | 220VAC ± 2% (230V or 240V re-settable via LCD panel) ) 110V ± 2% (100V,115V or 120V re-settable via LCD panel ) | |||||
Frequency | Synchronized ( Line mode); 50Hz or 60Hz +/-0.5% (Battery mode) | ||||||
Wave-form | True Sine wave | ||||||
Distortion | Tower | ≤3% (linear load) | ≤4% (linear load) | ||||
≤ 6% non-linear load) | ≤7% non-linear load) | ||||||
Rack | ≤4% (linear load) ,≤7% non-linear load) | ||||||
Overload Capacity | 125%~150%: 30 sec., .>150% : 200ms | ||||||
Crest Ratio | 03:01 | ||||||
Battery | DC Voltage | 36V | 96V | ||||
Capacity | 12V / 7Ah×3 pcs | 12V / 7Ah×8pcs | |||||
Back-up Time | >5min. | >9min. | > 5min. | ||||
Charger | Built-In /Option | 1Amp/8Amp | 1Amp/8Amp | ||||
Recharging Time | 5 hrs to 90% | ||||||
Bypass | Automatic | Overload or UPS fault | |||||
By setting | Voltage Range: 176~256V±20V (Re-settable via LCD panel) | ||||||
Transfer Time | 0 ms( 2.5ms inverter to bypass) | ||||||
Indicator | LCD (Series) | UPS status, I/P&O/P Voltage & Frequency ,Load %, Battery Voltage, Battery Capacity % ,Temperature, Model Spec., Event Log. | |||||
LED: Normal (Green), Warning (Yellow), Fault (Red) | |||||||
LED (Series) | Normal (Green), Bypass(Yellow), Battery Low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault (Red) | ||||||
Outlet | Tower | NEMAx3pcs or IEC320x4pcs | NEMAx6pcs or IEC320x6pcs | NEMAx6pcs or | |||
IEC320x3+ TBx1 | |||||||
Rack | NEMAx4pcs or IEC320x4pcs | NEMAx2+TBx1 or IEC320x4pcs | NEMAx2+TBx1 or IEC320x1+TBx1 | ||||
Audible Alarm | Battery Mode | Beeping every 4 seconds (re-settable) | |||||
Battery Low | Beeping every seconds | ||||||
Overload | Beeping twice per second | ||||||
Fault | Beeping Continuously | ||||||
Interface | RS-232 Interface | UPSilon2000 monitoring software for Windows all, Unix systems and Novell. | |||||
Multi-Interface Slot | SNMP card, AS 400, Dry Contact, USB Selectable | ||||||
Network | Surge Protection | RJ45 I/O port for Network or RJ 11 for Fax / Modem | |||||
Parallel | N/A | ||||||
Environment | Temperature | 0~40°C;32~104°F | |||||
Humidity | 0-95% non-condensing | ||||||
Acoustic Noise | <45 dBA ( at 1M ) | <50 dBA ( at 1 M) | |||||
Physical | Weight (w/o Batt.) | 6.5 kgs (Tower) | 13.5kgs (Tower) 9.5 kgs (Rack) | 14.5kgs (Tower) 10.5kgs (Rack) | |||
8.0 kgs (Rack) | |||||||
Weight (w/ Batt.) | 15 kgs (Tower) | 34 kgs (Tower) N/A (Rack) | 35 kgs (Tower) N/A (Rack) | ||||
15.5 kgs (Rack) | |||||||
Dim. | Tower | 160 x 220 x 400 mm | 200 x 352 x 450 mm | ||||
W*H*D | Rack | 440 x 88 x 465mm (Rack) | |||||
Color | White or Black |